31.2:

Simplified Synchronous Machine Model

JoVE 핵심
Electrical Engineering
JoVE 비디오를 활용하시려면 도서관을 통한 기관 구독이 필요합니다.  전체 비디오를 보시려면 로그인하거나 무료 트라이얼을 시작하세요.
JoVE 핵심 Electrical Engineering
Simplified Synchronous Machine Model

3 Views

01:30 min

November 21, 2024

The Synchronous Machine Model is a fundamental tool in analyzing and ensuring the transient stability of power systems. This model simplifies the representation of a synchronous machine under balanced three-phase positive-sequence conditions, assuming constant excitation and ignoring losses and saturation. The model is pivotal for understanding the behavior of synchronous generators connected to a power grid, particularly during transient events.

In this model, each generator is connected to a system that includes transmission lines, transformers, loads, and other machines, all of which are represented by an infinite bus behind a system reactance. The infinite bus concept assumes a constant voltage magnitude, phase, and frequency, serving as a reference point for system stability analyses.

When considering a synchronous generator connected to the grid, its output power is a sinusoidal function of the machine's power angle (δ). This relationship is expressed as:

Equation1

Where Vbus is the bus voltage, E' is the internal voltage of the generator, and Xeq is the reactance. During transient events, it is assumed that the internal voltage E and the bus voltage V remain constant, simplifying power calculations.

The Equal-Area Criterion is a graphical method used to assess the stability of the system following a sudden change in mechanical power. When a step change occurs, the rotor of the synchronous machine accelerates due to its inertia, overshooting its final steady-state position before stabilizing through the damping effects of mechanical and electrical losses. The criterion states that the area representing accelerating power (mechanical power minus electrical power) must equal the area representing decelerating power for the system to return to a stable operating point.

The Equal-Area Criterion is particularly useful for analyzing a single machine connected to an infinite bus or two interconnected machines. For more complex multi-machine systems, the transient stability analysis requires solving each machine's nonlinear swing equation using numerical integration techniques. This approach accounts for the interactions between multiple generators and determines the overall system stability and maximum power angle each generator can sustain.

In summary, the Synchronous Machine Model, complemented by the Equal-Area Criterion and numerical integration methods, provides a robust framework for analyzing and ensuring the transient stability of power systems. Understanding these concepts is essential for maintaining grid stability, especially in the face of disturbances and varying operating conditions.