Inductance: Single-Phase And Three-Phase Line

JoVE 핵심
Electrical Engineering
JoVE 비디오를 활용하시려면 도서관을 통한 기관 구독이 필요합니다.  전체 비디오를 보시려면 로그인하거나 무료 트라이얼을 시작하세요.
JoVE 핵심 Electrical Engineering
Inductance: Single-Phase And Three-Phase Line

3 Views

01:28 min

November 21, 2024

Understanding the inductance of transmission lines is crucial for efficient design and operation in electrical power systems. This discussion delves into the inductance characteristics of single-phase two-wire and three-phase three-wire transmission lines with equal phase spacing.

Single-Phase Two-Wire Line:

A single-phase line consists of two solid cylindrical conductors, denoted as x and y. Each conductor carries phasor currents ix and iy, respectively. Given that the sum of these currents is zero, we can calculate the total flux linking conductor x. This flux linkage is given by:

Equation1

Where rx' is the effective radius of conductor x, accounting for the proximity effect.

The inductance per conductor, Lx of conductor x, is then:

Equation2

Similarly, for conductor y, the flux linkage and inductance are computed. The total inductance of the single-phase circuit, also known as loop inductance, is:

Equation3

Three-Phase Three-Wire Line:

For a three-phase line, there are three solid cylindrical conductors, a, b, and c, each with equal radius r and equal phase spacing D. Assuming balanced positive-sequence currents, the total flux linking phase a is:

Equation4

From this, the inductance of phase a is derived:

Equation5

Due to symmetry, the same inductance applies to phases b and c. For a balanced three-phase operation, only one phase needs consideration since each phase's flux linkages are equal in magnitude and displaced by 120 degrees.

Understanding these inductance calculations helps in the design and analysis of transmission lines, ensuring minimal losses and optimal performance.