Primary distribution systems deliver electrical power from substations to consumers through various voltage classes, with 15-kV class voltages being predominant among U.S. utilities. Older 2.5- and 5-kV classes are being replaced by 15-kV primaries, while higher 25- to 34.5-kV classes are used in high-density urban areas and rural regions with long feeders. Three-phase, four-wire multigrounded systems are widely employed for balanced power delivery, using the neutral wire as a grounding point. Star-connected transformers at substations ensure efficient voltage step-down and grounding, while delta systems are used in older or industrial areas.
Rural areas typically utilize overhead lines with distribution transformers, fuses, and switches mounted on poles. In contrast, urban areas often use underground cable systems for reliability and aesthetic considerations, despite higher installation costs, as they offer significant protection from weather-related disruptions.
Types of Primary Distribution Systems
Radial System: Common in low-load-density areas, radial systems feature feeders extending radially from a substation. They are economical and simple but have limited reliability. Reclosers and sectionalizing switches are used to enhance reliability by isolating faults.
Loop Systems: Used in high-reliability areas, loop systems consist of feeders forming a loop, connecting back to the substation. This configuration ensures continuous power supply and flexibility in managing loads and isolating faults.
Primary Network Systems: Network systems are common in urban areas with high load densities. They provide the highest reliability and service quality and consist of a grid of interconnected feeders from several substations, with faults isolated by circuit breakers and fuses.
Primary distribution systems are vital for reliable and efficient power delivery. They cater to diverse geographical and load requirements, ensuring consistent supply to both urban and rural consumers.