In electrical power systems, understanding the capacitance of transmission lines is fundamental for efficient operation.

Single-Phase Lines

Consider a single-phase, two-wire transmission line with equal phase spacing energized by a voltage source. One conductor carries a uniform positive charge, while the other carries an equal negative charge. The capacitance C of the line can be derived from the voltage V between the conductors. For a one-meter section of the line, the capacitance is given by:

Equation1

Where ϵ is the permittivity of free space, D is the distance between the conductors, and r is the radius of the conductors. When the line is energized by a grounded center tap transformer, the voltage between each conductor and the ground, as well as the capacitance from either line to the grounded neutral, can be determined. This capacitance is represented in circuit models to accurately reflect the behavior of the transmission line under different operating conditions.

Three-Phase Lines

The analysis becomes more complex in three-phase transmission lines with equal phase spacing due to the interaction among the phases. For balanced positive-sequence voltages, the sum of the positive-sequence charges is assumed to be zero. The voltage between any two conductors is given by:

Equation2

where Dab, Dba, Dbc, Dac are the distances between the conductors, and qa, qb and qc are the charges on the respective conductors. The capacitance to neutral per unit length is given by:

Equation3

where D is the equivalent distance between the conductors, calculated using the geometric mean distance. Due to the symmetrical nature of balanced three-phase lines, this capacitance is the same for each phase.

A detailed understanding of these capacitance properties is crucial for accurately modeling and analyzing transmission lines, ensuring the efficient and reliable operation of power systems.